Understanding Static Electricity In Confined Space Entry Ventilation

Jan. 12, 2007
General Industry needs a clear well defined "How To" Standard on the proper procedures for controlling and safely removing electrostatic charges.

Working in tanks, manholes, and underground vaults are some of the most dangerous and potentially lethal occupations found in the industrial work environment. Federal, State, and corporate safety departments have written reams of documents and procedures on how to safely enter a confined space and perform some sort of maintenance, repair, or cleaning operation. Good corporate work practices and procedures have existed for years at the industry specific level. The phone companies, chemical, pharmaceutical, and oil storage and refineries have long seen the necessity of a "How To" manual for work on their own specific confined space hazards. The current OSHA Standard, 1910.146, Permit-required Confined Spaces goes a long way to providing General Industry the framework for entering and exiting a confined space and identifying some of the hazards a worker may encounter. This OSHA Standard was the outgrowth of many existing standards that came together to provide a minimum for General Industry to follow. The one process needed in the OSHA Standard is a specific work practice for the safe removal of static electricity during confined space ventilation.

Meeting Industry Demands
As a manufacturer, we have to be responsive to the wants and needs of our customers. Since the development and marketing of the first Saddle Vent® confined space entry ventilation system in the early 1990's, we have constantly been asked by companies, contractors, military, and consultants, "How do you properly handle the potential problem of static electricity build-up when you are ventilating a tank or manhole?" The art and science of ventilation has many books and articles to help in the quest for understanding the many techniques of ventilation used in industry. However, the one area that is very sketchy involves ventilation and the potential disastrous problems of electrostatic charges. Many of the corporate and government procedures reference that static charges should be removed but few tell the worker "How To Do It". After reviewing a great many standards and procedures, it appears that the best source for understanding this phase of the confined space ventilation procedure comes from an industry specific source, ANSI/API Standards 2015 and 2016, published by the American Petroleum Institute in Washington, D.C. These two documents provide requirements and actual procedures for safe entry and work in tanks and more specifically they address the issues with regard to controlling static electricity. The one ingredient missing in these standards is the aspect of "How To Set Up and Test" a good ventilation system.

Static Electricity-The Basics
At some time in our lives we have all felt the effect of static electricity build-up. Simply walking across the living room carpet and touching a metal doorknob or refrigerator and we feel and see the spark of discharged static electricity. I recently was filling my car with gasoline and I noticed a Warning Notice on the gas pump. The manufacturer of the gas pump very plainly and simply explained that if I get out of my car to put fuel in the tank, please do not get back in the car with fuel pumping until I touch the front frame of the car and discharge any potential build-up of static electricity or a resulting explosion could occur. This really caught my attention and the need for more specific treatment of the problem of static electricity in ventilation. Free electrons will be attracted to any other electron deficient nucleus. Movement of electrons from one atom to another constitutes what is referred to as electrical energy, including static electricity. What causes these electrons and static charges to migrate from one atom to another? This movement of static charges is due to such factors as a small change in temperature, atmospheric pressure, relative humidity, and the friction of air through a piece of ducting. The energy needed to cause this movement of atoms is surprisingly very low. Even though all matter contains free electrons, these electrons are unable to move freely through materials with high electrical resistance; these items are called dielectric. Standard non-conductive vinyl ducting is used in most confined space ventilation applications and even if it is properly grounded, the displaced electrons become trapped on the surface of the ducting or device in use. When a substance of opposite polarity comes in contact with a non-conductive device, the trapped electrons can flow freely between the two materials. This sudden and rapid transfer of electrons can cause a spark of sufficient intensity to ignite a confined space that may contain industrial solvents, methane gas from decaying material, hydrocarbon residue, or fine airborne dust. NIOSH references that a low relative humidity, below 50%, can accelerate the build-up of electrostatic charges creating sufficient energy to ignite flammable atmospheres. Abrasive blasting operations in confined spaces can cause a tremendous build-up of static charges by the mechanical friction of the blasting material and provide the charge necessary to cause an intense explosion of the dusty space.

The Proper Ventilation System
Both OSHA and ANSI/API Standards reference that good work practices in a confined space necessitates continuous ventilation before and during the work performed in a confined space. The objective of a good ventilation system is to first gas free the confined space and then to stabilize the space by providing continuous fresh air to the workers. ANSI/API recommends the use of a venturi type eductor air mover or an explosion-proof electric blower. The electric motor and on/off switches must be approved, at a minimum, for use in Class I, Division 1, Group D atmospheres for methane and Class II, Division 1, Groups E, F, and G for dust hazards. Each blower selected must have a metal grounding lug located on the blower. This lug is used to connect the ducting and its wire helix to the blower to form an electrical bond). Ducting should be supplied with fabric manufactured with a conductive coating material and a 12" grounding wire attached to the metal helix inside the duct and installed at each end of the duct. The bonding process is simply where metal components in the blower system are connected to form a conductive path that ensures electrical continuity and the flow of static electricity back to a safe grounded source. In performing tank work, the entire blower system is bonded to the tank that is connected to a proper earth ground. ANSI/API Standards 2015 and 2016 show detail how the use of a venturi style eductor along with an electric blower can be used to accomplish a preferred push/pull method of confined space ventilation. The one aspect of this ventilation set-up that is missing is how to test the system once it is in place. (What levels of resistance are sufficient to remove static charges?)

Revolutionary New Confined Space Entry Technique
Part of a good confined space entry program is having met key objectives listed in the OSHA 1910.146 and ANSI/API Standards; one important objective is the aspect of self rescue. The use of the Saddle Vent®, air conduit device, allows the worker to establish continuous ventilation in the confined space without obstructing the entry or egress of the workers. This device meets the objective of self-rescue for the workers who may encounter hazardous work environments. The second key objective is to provide a ventilation system that eliminates the build-up of static electricity and potential ignition hazard and provides for a safer work environment. The original Saddle Vent® device is now available in conductive plastic material. This Conductive Saddle Vent® connects to sections of conductive ducting and when properly assembled, forms a complete electrical circuit from the end of the duct all the way back to the grounded ventilation blower. Electrostatic charges that traditionally would build up on the surface of the ventilation system can now be safely removed through the ventilation system. A standard volt/ohm meter can be used to test the system for electrical resistance and assure an electrical path is present to remove electrostatic build-up. This is now called the Conductive Saddle Vent® Ventilation System.

Conclusion
Confined space entry is hazardous for even the most seasoned professionals. Unfortunately, most of the work done in confined spaces is done on an occasional basis with less than expert workers. It is only a matter of time when all the right conditions of fuel, oxygen, and ignition come together to form another newspaper or magazine headline. We believe that OSHA needs to seek the guidance and expertise of industry professionals to write additional "How To" procedures to aid and assist the occasional confined space worker on handling and removing static electricity when ventilating. The use of work specific devices like the Conductive Saddle Vent® System will eliminate one more potential hazard from the confined space worker's list of potential problems. This article is only a beginning in an effort to bring to light the need for more help in the area of worker safety with regard to confined space entry. Industry professionals from many disciplines must work together to develop safe working procedures for general industry with regard to controlling static electricity in the work environment. A detailed step-by-step method must be developed to set-up and properly test the conductive ventilation system.

Dave Angelico
Air Systems International, Inc.
www.airsystems.com

Sponsored Recommendations

Avetta Named a Leader in The Verdantix Green Quadrant: Supply Chain Sustainability Software 2024

Nov. 26, 2024
Avetta was named a leader by Verdantix in a 2024 sustainability software report for our ability to help clients and suppliers build sustainable supply chains.

Avetta is a Leader in Supply Chain Sustainability Software

Nov. 26, 2024
Verdantix has named Avetta a leader in its 2024 Green Quadrant for Supply Chain Sustainability Software. Download the report for independent insights into market trends and top...

The Power of Benchmarking in Procurement: Driving Success and Strategic Planning

Nov. 26, 2024
Explore the strategic impact of benchmarking in procurement to drive success and plan effectively.

What We Can Learn From OSHA's 2024 Top 10 Safety Violations

Nov. 26, 2024
Learn what OSHA’s 2024 top 10 incident list reveals about the limitations of compliance and the need for proactive, continual safety improvement.

Voice your opinion!

To join the conversation, and become an exclusive member of EHS Today, create an account today!